Yellow THHN
Featuring dual certification to UL83 and CSA22.2 NO.75, our yellow THHN/THWN-2/T90 nylon-jacketed wire delivers robust performance with 90°C heat tolerance, chemical resistance, and versatility in damp locations. The vibrant yellow hue enhances visibility in low-light conditions, making it ideal for applications that require clear signaling and control, such as warning systems and automated equipment.
Specification
Conductor | Insulation Thickness (mils) |
Jacket Thickness (mils) |
Nominal O.D. (mils) |
Approx. Net Wt. Per 1000′ (lbs.) |
Allowable Ampacities+ | |||
---|---|---|---|---|---|---|---|---|
60°C | 75°C | 90°C | ||||||
14* | 1 | 15 | 4 | 102 | 15 | 15 | 15 | 15 |
12* | 1 | 15 | 4 | 119 | 23 | 20 | 20 | 20 |
10* | 1 | 20 | 4 | 150 | 36 | 30 | 30 | 30 |
14* | 19 | 15 | 4 | 109 | 16 | 15 | 15 | 15 |
12* | 19 | 15 | 4 | 128 | 24 | 20 | 20 | 20 |
10* | 19 | 20 | 4 | 161 | 38 | 30 | 30 | 30 |
8 | 19 | 30 | 5 | 213 | 63 | 40 | 50 | 55 |
6 | 19 | 30 | 5 | 249 | 95 | 55 | 65 | 75 |
4 | 19 | 40 | 6 | 318 | 152 | 70 | 85 | 100 |
3 | 19 | 40 | 6 | 346 | 189 | 85 | 100 | 115 |
2 | 19 | 40 | 6 | 378 | 234 | 95 | 115 | 130 |
1 | 19 | 50 | 7 | 435 | 299 | 110 | 130 | 145 |
1/0 | 19 | 50 | 7 | 474 | 372 | 125 | 150 | 170 |
2/0 | 19 | 50 | 7 | 518 | 462 | 145 | 175 | 195 |
3/0 | 19 | 50 | 7 | 568 | 575 | 165 | 200 | 225 |
4/0 | 19 | 50 | 7 | 624 | 718 | 195 | 230 | 260 |
250 | 37 | 60 | 8 | 694 | 851 | 215 | 255 | 290 |
300 | 37 | 60 | 8 | 747 | 1012 | 240 | 285 | 320 |
350 | 37 | 60 | 8 | 797 | 1174 | 260 | 310 | 350 |
400 | 37 | 60 | 8 | 842 | 1334 | 280 | 335 | 380 |
500 | 37 | 60 | 8 | 926 | 1655 | 320 | 380 | 430 |
600 | 61 | 70 | 9 | 1024 | 1987 | 350 | 420 | 475 |
750 | 61 | 70 | 9 | 1126 | 2464 | 400 | 475 | 535 |
1000 | 61 | 70 | 9 | 1275 | 3257 | 455 | 545 | 615 |
* Sizes 14, 12, and 10 AWG are available with Technology only in Barrel configurations. Standard put ups vary from the ones shown on this chart for standard 14-10 AWG THHN
+Allowable ampacities shown are for general use as specified by the 2014 Edition of the National Electrical Code Sections 310.15 and 240.4(D)
Unless the equipment is marked for use at higher temperatures the conductor shall be limited to the following per NEC 110.14(C):
- 60°C – When terminated to equipment for circuits rated 100 amperes or less or marked for 14 – 1 AWG conductors
- 75°C – When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG
- 90°C – THHN dry locations and THWN-2 wet or dry locations for ampacity adjustment purposes using NEC section 310.15
Application
- Control circuits in manufacturing equipment, like conveyor belts and robotics, where yellow wiring supports easy identification of signals for maintenance.
- Warning and caution systems in construction sites or factories, utilizing the color’s high contrast for accident prevention.
- Security and alarm panels in residential and commercial settings, for dependable signal transmission.
- Industrial control panels, where yellow wires act as auxiliary circuits in motor controls for seamless operation.
JZD Factory
JZD Wire & Cable has been established for over 25 years, We are manufacturing and supplying quality electrical cables to America, Canada, European countries, Philippines. Australia, South American countries, South Africa, ect. JZD Wire & Cable makes customized cables for a complete range in this industry, including single and multi-cores cables, such as : Solar Cable, THHN Nylon Cable, Building wire, Flat TPS Cable, AC Cable, MC Cable, NM-B, NMD90, Fire rated cable, Silicone Cable, ect. High quality products that JZD provided have been taken part in lots of buildings and projects all over the world. Like airports, schools, hospitals, factories, ect.
Certification
Exhibitation
April 2025 Exhibition in Indonesia
May 2025 Exhibition in the Philippines
FAQ
Q: Are you a manufacturer or trading company?